LH/AD-T
Deflagration Flame Arrester, short time burning-proof, End-of-Line

Características
Función y descripción

Protection Against Atmospheric Deflagrations
The PROTEGO® LH/AD-T End-of-Line Deflagration Flame Arrester provides protection against flame transmission through atmospheric deflagration and short time burning on the flame arrester element. The device is typically installed on vent lines of vessels and plant equipment which are not pressurized. The device is equipped with a temperature sensor which immediately detects a flame on the FLAMEFILTER® surface.
Protection Against Short-Time Burning
After the flame is detected, a secondary measure, such as inerting or closing of a shut-off valve to block the vapor flow to the device, should activate within 60 seconds and extinguish the flame so that the system can operate safely. The device prevents flame transmission from short time burning and atmospheric deflagration into the vessel or plant.

Main Component – PROTEGO® Flame Arrester Unit
The PROTEGO® LH/AD-T consists of the housing (1), a weather hood (2), and the PROTEGO® Flame Arrester Unit (3). The device is equipped with a metal weather hood. The FLAMEFILTER® (4) gap size depends on the device’s intended use. Specifying the operating conditions, such as the temperature, explosion group, and the composition of the fluid, enables PROTEGO® to select the best End-of-Line Deflagration Flame Arrester for your application.

For Explosion Groups IIA to IIC
The PROTEGO® LH/AD-T Series End-of-Line Deflagration Flame Arrester is available for substances from explosion groups IIA to IIC (NEC groups D to B). The standard design can be used with an operating temperature of up to +60°C / 140°F. Devices with special approval for higher temperatures are available upon request. EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Dimensiones
To select the nominal size (DN), please use the flow capacity charts on the following pages
| DN | a | b | c* | c* |
| IIB3 | IIC | |||
| 50 / 2" | 100 / 3.94 | 240 / 9.45 | 530 / 20.87 | 550 / 21.65 |
| 80 / 3" | 150 / 5.91 | 295 / 11.61 | 560 / 22.05 | 580 / 22.83 |
| 100 / 4" | 200 / 7.87 | 350 / 13.78 | 585 / 23.03 | 605 / 23.82 |
| 150 / 6" | 300 / 11.81 | 600 / 23.62 | 630 / 24.80 | 655 / 25.79 |
| 200 / 8" | 300 / 11.81 | 600 / 23.62 | 630 / 24.80 | 655 / 25.79 |
| 250 / 10" | 400 / 15.75 | 800 / 31.50 | 750 / 29.53 | 770 / 30.31 |
| 300 / 12" | 400 / 15.75 | 800 / 31.50 | 740 / 29.13 | 760 / 29.92 |
| 350 / 14" | 600 / 23.62 | 1000 / 39.37 | 800 / 31.50 | 820 / 32.28 |
| 400 / 16" | 600 / 23.62 | 1000 / 39.37 | 790 / 31.10 | 815 / 32.09 |
| 500 / 20" | 700 / 27.56 | 1200 / 47.24 | 810 / 31.89 | 835 / 32.87 |
| 600 / 24" | 800 / 31.50 | 1200 / 47.24 | 935 / 36.81 | 960 / 37.80 |
| 700 / 28" | 1000 / 39.37 | 1500 / 59.06 | 975 / 38.39 | 995 / 39.17 |
| 800 / 32" | 1200 / 47.24 | 1700 / 66.93 | 1015 / 39.96 | 1035 / 40.75 |
Dimensiones en mm / pulgadas
* c are reference values. Exact measures depend on the flange connection.
Selección de materiales para la vivienda
| Design | A | B |
| Housing | Steel | Stainless Steel |
| Weather Hood | Stainless Steel | Stainless Steel |
| Protection screen | Stainless Steel | Stainless Steel |
| Flame arrester unit | A, B | B |
Special materials upon request
Combinación de materiales para la unidad apagallamas
| Design | A | B |
| FLAMEFILTER® cage | Steel | Stainless Steel |
| FLAMEFILTER® | Stainless Steel | Stainless Steel |
Special materials upon request
Selección del grupo de explosión
| MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| ≥ 0,65 mm | IIB3 | C |
| < 0,5 mm | IIC | B |
Special approvals upon request
Especificación de la máx. temperatura de operación
| ≤ 60°C / 140°F | Tmaximum allowable operating temperature in °C |
| - | Designation |
higher operating temperatures upon request
Tipo de bridas de conexión
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other types upon request
Modelo y especificación
Following designs are available:Special designs available on request
Diagrama de flujo volumétrico
Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.