UB/VF

UB/VF

Vacuum Diaphragm Valve deflagration-proof

Функция и описание

The deflagration-proof UB/VF type PROTEGO® diaphragm valve is a state-of-the-art vacuum relief valve combining the function of a dynamic and static flame arrester. Worldwide this design is unique. It is primarily used as a safety device for flame transmission proof inbreathing on tanks, containers and process engineering apparatus. The valve offers reliable protection against vacuum build up, prevents the inbreathing of air and product losses almost up to the set vacuum and protects against atmospheric deflagration. The PROTEGO® UB/VF diaphragm valve has proven its performance over many years in a great variety of severe applications in the petrochemical and chemical industry. Worldwide it is the only vent which functions in services such as styrene and acrylics. The set vacuum is adjusted with a freeze resistant water-glycol mixture, which assures safe operation under extreme cold weather conditions. The PROTEGO® UB/VF valve is available for substances from explosion group IIB3 (NEC group C MESG ≥ 0.65 mm).

If a vacuum builds up in the tank, it is transmitted through pressure balancing tubes into the vacuum chambers (1), (2). If the set vacuum, which depends on the liquid column height in the vacuum chamber, is reached the atmospheric pressure lifts the diaphragm (3) up off the inner and outer valve seat rings (4,5). Ambient air can now flow into the tank. The liquid column heights, which affect the set vacuum, can be checked by a floating level indicator (6).

The tank vacuum is maintained up to the set vacuum with a tightness that is far superior to the conventional standard due to our highly developed manufacturing technology. This is achieved because the liquid loaded diaphragm presses tightly around the special designed valve seat surface area, even when the operating vacuum increases. This is extremely important to reduce leakage to an absolute minimum. After the vacuum is balanced, the valve reseats and provides a tight seal.

At very low vacuum settings the explosion pressures resulting from an atmospheric deflagration may be strong enough to lift the diaphragm off the valve seat rings so that flashback could result. The ignition into the tank can be prevented by installing the PROTEGO® flame arrester unit (7). This flame arrester unit provides additional protection against atmospheric deflagration during regular maintenance and inspection.

The valve can be used up to an operating temperature of +60°C/ 140°F and meets the requirements of European tank design standard EN 14015 – Appendix L and ISO 28300 (API 2000).

Type-approved in accordance with the current ATEX Directive and EN ISO 16852 as well as other international standards.

Особые признаки и преимущества

  • high performance seal reducing product loss below EPA’s 500ppm rule preventing environmental pollution
  • set vacuum close to the design vacuum enables optimum pressure maintenance in the system
  • high flow capacity
  • can be used as a protective system according to ATEX in areas subject to an explosion hazard
  • protection against atmospheric deflagrations for products up to explosion group IIB3 (NEC group C MESG ≥ 0.65 mm)
  • minimum pressure drop of the FLAMEFILTER®
  • freeze protection at sub-zero conditions
  • self draining function for condensate
  • liquid column height is monitored by level indicators
  • easy maintenance through hinged vent cap
  • modular design enables individual FLAMEFILTER® discs and valve diaphragm to be replaced
  • particularly suitable for problematic products such as styrene, acrylics, etc

Таблица параметров

To select the nominal size (DN), please use the flow capacity charts on the following pages

DNvacuum vacuum 80 / 3" vacuum vacuum100 / 4" 150 / 6"
aup to -28 mbarup to -11.2 inch W.C.615 / 24.21up to -22 mbarup to -8.8 inch W.C.645 / 25.39680 / 26.77
a< -28 mbar< -11.2 inch W.C.765 / 31.12< -22 mbar< -8.8 inch W.C.795 / 31.30830 / 32.68
b410 / 16.14485 / 19.09590 / 23.23
DNvacuum vacuum 80 / 3" vacuum vacuum100 / 4" 150 / 6"
aup to -28 mbarup to -11.2 inch W.C.615 / 24.21up to -22 mbarup to -8.8 inch W.C.645 / 25.39680 / 26.77
a< -28 mbar< -11.2 inch W.C.765 / 31.12< -22 mbar< -8.8 inch W.C.795 / 31.30830 / 32.68
b410 / 16.14485 / 19.09590 / 23.23

размер в мм Dimensions for vacuum diaphragm valve with heating coil upon request

UB/VF

Выбор материала корпуса

Design CD
HousingCast IronStainless Steel
Valve topStainless SteelStainless Steel
Heating coil (UB / VF-H-...)Stainless SteelStainless Steel
Valve seatStainless SteelStainless Steel
GasketFPMPTFE
DiaphragmA, BA, B
Flame arrester unitAC
Design CD
HousingCast IronStainless Steel
Valve topStainless SteelStainless Steel
Heating coil (UB / VF-H-...)Stainless SteelStainless Steel
Valve seatStainless SteelStainless Steel
GasketFPMPTFE
DiaphragmA, BA, B
Flame arrester unitAC

Option: Housing with ECTFE-liningSpecial materials upon request

Material selection

DesignAB
DiaphragmFPMFEP
DesignAB
DiaphragmFPMFEP

Special materials upon request

Комбинация материалов элемента огнепреградителя

Design C
FLAMEFILTER® cageStainless Steel
FLAMEFILTER®Stainless Steel
SpacerStainless Steel
Design C
FLAMEFILTER® cageStainless Steel
FLAMEFILTER®Stainless Steel
SpacerStainless Steel

Special materials upon request

UB/VF

Выбор группы взрывоопасности

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,65 mmIIB3C
MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,65 mmIIB3C

Special approvals upon request

Вид фланцевого соединения

EN 1092-1; Form B1
ASME B16.5; 150 lbs RFSF
EN 1092-1; Form B1
ASME B16.5; 150 lbs RFSF

other types upon request

Модели и спецификация

The diaphragm is pressurized by liquid.
Vacuum diaphragm valve, basic design

UB/VF - –

Vacuum diaphragm valve with heating coil (max. heating fluid temperature +85°C / 185°F)

UB/VF - H

Vacuum diaphragm valve, basic design

UB/VF - –

Vacuum diaphragm valve with heating coil (max. heating fluid temperature +85°C / 185°F)

UB/VF - H

In addition to the standard design, a series of specially developed designs, which are particularly suitable for operating conditions to which these products are subjected, can be provided upon request (for example, for acrylics or styrene storage tanks, etc.).

Settings

Vacuum:

-3.5 mbar -35 mbar
-1.4 inch W.C. -14 inch W.C.
Higher and lower vacuum settings upon request
UB/VF

Диаграммы пропускной способности

Диаграммы пропускной способности были определены с помощью калибрированной и сертифицированной объединением технического надзора (TÜV) проточной измерительной установки. Пропускная способность V. в м³/час определена воздухом при нормальных атмосферных условиях в соответствии с ISO 6358 (20°C, 1 бар). Преобразование для различных плотностей и температур см. главу 1: Технические основы

UB/VF
UB/VF