SV/E

SV/E

Vacuum Relief Valve deflagration-proof

Функция и описание

The deflagration-proof SV/E type PROTEGO® valve is a state of the art vacuum relief valve with an integrated flame arrester unit. It is primarily used as a safety device for flame transmission proof inbreathing on tanks, containers and process engineering apparatus. The valve offers reliable protection against vacuum and prevents inbreathing of air almost up to the set pressure; it also protects against atmospheric deflagration. The PROTEGO® flame arrester unit is designed to achieve minimum pressure drop with maximum safety. The PROTEGO® SV/E valve is available for substances from explosion groups IIA to IIC.

When the set vacuum is reached, the valve starts to open and reaches full lift within 10% overpressure. This unique 10% technology enables a set vacuum that is only 10% above the maximum allowable working vacuum (MAWV) of the tank. After years of development, this typical opening characteristic of a safety relief valve is now also available for the low pressure range. The tank pressure is maintained up to the set vacuum with a tightness that is far superior to the conventional standard due to our state of the art manufacturing technology. This feature is ensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1) or with an air cushion seal (2) in conjunction with high quality FEP diaphragm. The valve pallets are also available with a PTFE seal to prevent the valve pallets from sticking when sticky products are used and to enable the use corrosive fluids. After the vacuum is equalized, the valve reseats and provides a tight seal.

If the valve is used in atmospheres forming an explosive mixture with air and the mixture ignites, the integrated PROTEGO® flame arrester unit (3) prevents flame transmission into the tank.

The standard design is tested at an operating temperature up to +60°C / 140°F and meets the requirements of European tank design standard EN 14015 – Appendix L and ISO 28300 (API 2000). In addition numerous versions for higher operating temperature are available.

Type-approved in accordance with the current ATEX Directive and EN ISO 16852 as well as other international standards. Additional certificates from classification associations for use on ships are also available.

Особые признаки и преимущества

  • requires only 10% overpressure to full lift
  • extreme tightness and hence least possible product losses and reduced environmental pollution
  • through 10% technology lower set vacuum can be reached which results in product loss reduction compared to conventional 40% and 100% overpressure technology vents (compare API 2000)
  • optimized flow performance
  • the valve disc is guided within the housing to protect against harsh weather conditions
  • can be used as protective system according ATEX in areas subject to explosion hazards
  • FLAMEFILTER® provides protection against atmospheric deflagration
  • FLAMEFILTER® integrated into the valve saves space, weight and reduces cost
  • FLAMEFILTER® protected from clogging through product vapour
  • PROTEGO® flame arrester unit has a low pressure drop
  • maintenance friendly design
  • modular design enables individual FLAMEFILTER® and valve pallets to be replaced
  • an additional lifting gear can be purchased

Таблица параметров

To select the nominal size (DN), please use the flow capacity chart on the following page

DN50 / 2'' 80 / 3'' 100 / 4" 150 / 6'' 200 / 8'' 250 / 10''300 / 12''
a140 / 5.51170 / 6.69190 / 7.48230 / 9.06300 / 11.81325 / 12.80425 / 16.73
b105 / 4.13115 / 4.53125 / 4.92165 / 6.50195 / 7.68230 / 9.06280 / 11.02
c225 / 8.86240 / 9.45320 / 12.60410 / 16.14460 / 18.11525 / 20.67575 / 22.64
d170 / 6.69235 / 9.25280 / 11.02335 / 13.19445 / 17.52505 / 19.88505 / 19.88
e215 / 8.46215 / 8.46255 / 10.04345 / 13.58435 / 17.13470 / 18.50635 / 25.00
DN50 / 2'' 80 / 3'' 100 / 4" 150 / 6'' 200 / 8'' 250 / 10''300 / 12''
a140 / 5.51170 / 6.69190 / 7.48230 / 9.06300 / 11.81325 / 12.80425 / 16.73
b105 / 4.13115 / 4.53125 / 4.92165 / 6.50195 / 7.68230 / 9.06280 / 11.02
c225 / 8.86240 / 9.45320 / 12.60410 / 16.14460 / 18.11525 / 20.67575 / 22.64
d170 / 6.69235 / 9.25280 / 11.02335 / 13.19445 / 17.52505 / 19.88505 / 19.88
e215 / 8.46215 / 8.46255 / 10.04345 / 13.58435 / 17.13470 / 18.50635 / 25.00

размер в мм

SV/E
Detail X
Detail X

Выбор материала корпуса

Design
BC
Housing
Steel Stainless Steel
Heating jacket (SV / E-(S)-H-...)
Steel
Stainless Steel
Valve seat
Stainless Steel Stainless Steel
Gasket
PTFE
PTFE
Flame arrester unit
B B
Design
BC
Housing
Steel Stainless Steel
Heating jacket (SV / E-(S)-H-...)
Steel
Stainless Steel
Valve seat
Stainless Steel Stainless Steel
Gasket
PTFE
PTFE
Flame arrester unit
B B

Special materials upon request

Комбинация материалов элемента огнепреградителя

Special materials upon request

Material selection for valve pallet

DesignABCDEF
Vacuum range [mbar]
 [inch W.C.]
-2.0 up to -3.5
 -0.8 up to -1.4
<-3.5 up to -14
 <-1.4 up to -5.6
<-14 up to -35
 <-5.6 up to -14
<-35 up to -60
 <-14 up to -24
<-14 up to -35
 <-5.6 up to -14
<-35 up to -60
 <-14 up to -24
Valve palletAluminiumStainless SteelStainless SteelStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalMetal to MetalPTFEPTFE
DesignABCDEF
Vacuum range [mbar]
 [inch W.C.]
-2.0 up to -3.5
 -0.8 up to -1.4
<-3.5 up to -14
 <-1.4 up to -5.6
<-14 up to -35
 <-5.6 up to -14
<-35 up to -60
 <-14 up to -24
<-14 up to -35
 <-5.6 up to -14
<-35 up to -60
 <-14 up to -24
Valve palletAluminiumStainless SteelStainless SteelStainless SteelStainless SteelStainless Steel
SealingFEPFEPMetal to MetalMetal to MetalPTFEPTFE

Special materials and higher pressure settings upon request

SV/E
Detail X
Detail X

Выбор группы взрывоопасности

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,65 mm IIB3 C
≥ 0,50 mm IIB B
< 0,50 mm IIC B
MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,65 mm IIB3 C
≥ 0,50 mm IIB B
< 0,50 mm IIC B

Special approvals upon request

Спецификация макс. рабочей температуры

≤ 60°C / 140°FTmaximum allowable operating temperature in °C
-Designation
≤ 60°C / 140°FTmaximum allowable operating temperature in °C
-Designation

higher operating temperatures upon request

Вид фланцевого соединения

EN 1092-1; Form B1
ASME B16.5; 150 lbs RFSF
EN 1092-1; Form B1
ASME B16.5; 150 lbs RFSF

other types upon request

Модели и спецификация

The valve disc is weight-loaded. Higher vacuum can be achieved upon request with a special spring loaded design.
There are four different designs:
Vacuum relief valve, basic design

SV/E- – - –

Vacuum relief valve with heating jacket (max. heating fluid temperature +85°C / 185°F)

SV/E- – - H

Vacuum relief valve with lifting gear (ship design)

SV/E- S - –

Vacuum relief valve with lifting gear (ship design) and heating jacket (max. heating fluid temperature +85°C / 185°F)

SV/E- S - H

Vacuum relief valve, basic design

SV/E- – - –

Vacuum relief valve with heating jacket (max. heating fluid temperature +85°C / 185°F)

SV/E- – - H

Vacuum relief valve with lifting gear (ship design)

SV/E- S - –

Vacuum relief valve with lifting gear (ship design) and heating jacket (max. heating fluid temperature +85°C / 185°F)

SV/E- S - H

Additional special devices available upon request

Settings

Vacuum:

-2.0 mbar -60 mbar (-0.2 kPa up to -6 kPa)
-0.8 inch W.C. -24 inch W.C.
Higher vacuum settings upon request
SV/E
Detail X
Detail X

Диаграммы пропускной способности

Диаграммы пропускной способности были определены с помощью калибрированной и сертифицированной объединением технического надзора (TÜV) проточной измерительной установки. Пропускная способность V. в м³/час определена воздухом при нормальных атмосферных условиях в соответствии с ISO 6358 (20°C, 1 бар). Преобразование для различных плотностей и температур см. главу 1: Технические основы

SV/E
Detail X
Detail X
SV/E
Detail X